Welcome to your one-stop Critical Infrastructure store for business Resilience - CALL 1300 853 942

Galaxy VS UPS 40kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5x8

POA
Taxes, discounts and shipping calculated at checkout.
Schneider Electric SA  |  SKU: GVSUPS40K0B4HS

Galaxy VS UPS 40kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5x8 is backordered and will ship as soon as it is back in stock.


Other Equivalent Brands

Contact Us

Speak to Treske to see how we can help you critical infrastructure needs/become more resilient.

Schneider Electric SA

Galaxy VS UPS 40kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5x8

POA
Overview
Presentation Highly efficient, easy-to-deploy 40kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 4 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5x8 start-up service.
Lead time Usually Ships within 2 Weeks
Main
Main Input Voltage 400 V 3 phases
Other Input Voltage 380 V
415 V
Main Output Voltage 400 V 3 phases
Other Output Voltage 380 V
415 V
Rated power in W 40 kW
Rated power in VA 40 kVA
Battery type Internal modular battery
VRLA
Provided equipment Dust filter
Installation manual
Integrated network management
Start-up service
EcoStruxure Ready
Batteries & Runtime
Efficiency

View Efficiency Graph
Battery voltage 480 V
Discharge battery voltage 384 V
Max current discharge 109 A
Battery power in VAH 0 VAh runtime
Extended runtime 0
General
Redundant No
Product or component type Uninterruptible power supply (UPS)
Physical
Colour White
Height 148.5 cm
Width 52.1 cm
Depth 84.7 cm
Net weight 200 kg
USB compatible No
Input
Network frequency 40...70 Hz
Input voltage limits 340...460 V 400 V
Maximum input current 72 A
Max short time withstand current 65 kA
Input harmonic distortion Less than 3 % for full load
Load power factor From 0.7 leading to 0.7 lagging without any derating
Input Power Factor at Full Load 0.99
View product